Typically they dont land on the desk of top decision-makers
or lend themselves to innovative applications. Andy Rudderham,
vice president of sales for Total Systems Ltd. in Mississauga,
ON, says equipment dealers and gen set packagers are the only
ones likely to get fired up about them. But whether you call
them block heaters, water jacket heaters, or engine preheaters,
theyre essential to getting diesel-fueled gen sets up
and running at full power in the 10 seconds that are standard
for emergency power applications.
Wayne Bass, market manager, engine and industrial distributors,
for Kim Hotstart, which supplies heaters to Generac Power
Systems Inc., Katolight Corp., Detroit Diesel, Caterpillar,
and Kohler, among others, reminds us that coming online at
an engines rated rpms and assuming a full load
within the 10-second window specified in NFPA standard 110
and Canadian CSA 282 requires maintaining engine temperature
between 100†F to 120†F. Bass also maintains that, in addition
to easier starts, block heaters save engine warm-up time and
help reduce fuel, plus engine wear90% of which he attributes
to low water jacket temperature. Scott Phillips, technical
communicator for the Power Systems Division of Wagner Equipment
Co., a Caterpillar distributor in Albuquerque, NM, agrees.
On large engines, where the pistons may be 6 inches
across, starting dry and cold makes for wear. Starting at
100†F to 120†F youll have oil pressure, which means
less metal to metal.
All things considered, says Rudderham, block heaters dont
get much attention because theyre standard. Total Systems
Ltd. is a dealer for Generac Power Systemsamong other
land and marine engine manufacturersand services approximately
3,000 gen set installations nationwide, along with standby
equipment it maintains in its own building. Were
in the generator business, says Rudderham, so
we wouldnt dream of having a generator set without a
block heater and without proper maintenance to assure that
the engine starts when we need it to. When the power goes
out, our phones light up like Christmas trees.
Total Systems emergency power is supplied by a Generac
model SD080 diesel generator, 60 kW (347/600 V three-phase),
which is in a Level 11 sound-attenuated enclosure and equipped
with an 1,800 W, 120 V Kim Hotstart block heater, a double
walled basetank for 36+ hours of runtime, a battery blanket,
and a remote annunciator panel for indoor annunciation of
any faults. Manager of technical services Mike August considers
the 1,800-W heater standard for the size of the gen set and,
although the unit is located outside the headquarters building,
because its enclosed, no extra block heater fire power
was required. If the unit were sitting out in the middle
of a field where it wasnt sheltered from wind, for example,
you certainly would want to beef up the heater or add a second
one, says August.
| |
 |
 |
|
An engine block heater is not important until it doesnt
work, says Mike Dauffenbach, eastern regional manager
for Katolight Inc., which uses Kim Hotstart heaters on gen
sets it packages. There are all kinds of people out
there operating engine generator sets, and jacket water heaters
are not a big issue. Except when they dont work.
Bass agrees, We dont hear horror stories from
clients as much as apprehension. In the fall we start to get
callsfrom hospitals, for example, where a heater has
stopped working and they need us to send a new element right
awayits a pretty common experience.
The tank-type block heaters Kim Hotstart manufactures are
designed to heat and circulate coolant through the entire
engine block by way of thermal siphon action. The heated coolant
rises, seeking the path of least resistance, and pushes cold
water out to be heated. A thermostat turns the heater on and
off to keep the coolant at the right temperature.
Some people use heaters that are meant for automotive
applications, says Dauffenbach. These are designed
to be plugged in when its cold and then unplugged, and
when theyre operated in automatic position on a stationary
engine, they dont have the life of an industrial-grade
heater. The fact is that any heater that is sized properly
will keep the block warm. And the way we size the heaters
depends on the application. If were sizing for an ambient
temperature that doesnt go below zero, we use one size,
but if were sizing for something here in Minnesota where
it goes 20 below, we use a larger heater. Otherwise the heat
will dissipate faster than the heater can make it. In the
end, what it boils down to is that the thermodynamics of sizing
a heater are based on the amount of water you want to heat,
the surface area of the engine, and the temperature differential.
A diesel engine is a cold-blooded animal when the outside
temperature is extremely cold, says Bryon Carlson, project
manager at Generac Power Systems, which also uses Kim Hotstart
heaters. Not only is the diesel fuel cold, but so is
the air coming in from outside. The idea is to heat the block
to allow combustion to take place at a faster rate on initial
start up. You cant do a whole lot about the air unless
you have air heaters, but you can do something to keep the
area around your cylinders warm, which allows your combustion
to happen much more reliably. We send gen sets to Puerto Rico
and South America without block heaters, places where the
temperature is routinely 75†F to 80†F or higher, but we have
a lot of customers along the gold coast in Florida and in
warm spots in California, and they all have block heaters.
As most generator manufacturers, we size by cubic inch
of engine. Watts per cubic inch is the rule of thumb. We give
customers a choice, from whats called normal heating,
which is 3 watts per cubic inch, up to whats called
an Arctic package, which is 5 watts per cubic inch, meaning
that you get that much more watt per cubic inch of input of
heat. If you go with a little bit higher heater, youll
end up drawing a little more electricity, but youre
going to retain your heat better. Given the same application,
a smaller heater is likely to run longer. But the fact is
most of our customers are dealers who have been in the market
and are quite knowledgeable. We ship the gen sets with the
heaters already on, plumbed, and tested.
At Katolight, every engine generator that we have in
our catalog has a jacket water heater on it as a standard
item, says Dauffenbach. And this is because we
want the installation to work reliably. The single-phase heater
is by far the most common heater we install. But if were
supplying a large engine, where we might have a couple of
5,000-W heaters, its best to use 240 V because you can
draw less amps with a higher voltage and keep wire size down.
If we get into a case where we have a heavy-duty industrial
application, a three-phase heater is a better option, a 208
V or 480 V. The big advantage of a three-phase heater is its
much cheaper to operate.
If a pump makes circulation more reliable, then we
put a pump on---typically on large 12- and 16-cylinder engines
[Kim Hotstart recommends forced circulation on engines 20
L or larger]. We also use pumps on engines where the thermal
siphon doesnt work well because of the geometry of the
engine. If you have an engine thats compartmentalized,
the thermal siphon doesnt work very efficiently. Plus
you have two heaters, one on each side of the V, and a pump
will circulate the water better. This kind of decision-making
is specific to the engine manufacturer.
Phillips says that the Wagner CAT dealership installs valves
on larger engines You can shut the valve on both sides,
and when it comes time, all you have to do is drain whatever
is in the hoses and the tank of the block heater. Otherwise
youre going to have to drain the entire cooling system.
There are other applications besides standby situations
where block heaters are important, says Phillips. We
have customers who run aggregate pits where they make gravel
and road product. Theyll run a nighttime generator to
keep their asphalt warm, and they have jacket water heaters
on the engines because they make for less wear and tear on
start-up.
Another application is where low emissions are a factor.
Diesel engines tends to over-fuel and when the combustion
temperature is low the fuel isnt burned as well, which
produces more raw smoke. When the combustion temperature is
hotter it lowers your emissions.
Although engine block heater manufacturers typically issue
recommendations that match heater size to the size of an engine,
Rudderham says some block heaters still arent specd
properly. From a practical standpoint, the further north
we go the more often we find block heaters undersized. The
specs may call for 1,500 watts but to really keep the block
as warm as it needs to be for reliable starting, whats
needed is 2,500 watts. If we discover this upfront, we install
a new heater off the shelf before the engine goes onsite.
Other times we find out the hard way. We might not know where
the generator is ending up, for example, and when we get called
for a start-up, well discover its been installed
where the air is colder than normal, and during testing the
engines hard starting.
The other thing youll find is that sometimes
engineers dont know. They have their standard specs,
and sometimes they dont look as closely as they should
at block heaters. They specify, Must have block heater,
but what does that mean500 watts or 5,000 watts? Depending
on where you are, one would be more appropriate than another.
Also its logical that people typically bid to minimum
specifications because they dont want to be priced out
of the competition. But once the job is awarded the challenge
becomes how to make whats been purchased work. I dont
think people intentionally cut corners. Its more a function
of misapplication and misinformation.
But if block heaters are such no-nonsense equipment, why
does Kim Hotstart routinely get cold-weather calls?
Block heater maintenance, which most gen set manufacturers
suggest should be no big deal, turns out to be a culprit.
With proper maintenance and care, says Rudderham,
these heaters should last indefinitely. But its
like everything else. If you abuse themif theyre
undersized and theyre running all the timeits
not uncommon that when we service a gen set well replace
the block heater. Which means that while the ultimate end
user isnt involved in the initial selection process,
theyre likely to be pulled in if something doesnt
go right. Customers think theyre getting something that
works, and they dont like discovering that they have
to pay someone like us to come out and advise them on a better
way of doing things.
Its like batteries. Just because a generator
has batteries doesnt mean theyre any good. Are
they the right size? Do they have enough cold cranking amps?
Its also not uncommon for the heater to be hooked up
incorrectly, like a 240-V block heater hooked up to 120-V
power.
Not hooking the unit up at all can also be a problem. In
any type of cold weather climate its just plain and
simple that if a diesel engine is cold, it wont start,
says Carlson. So customers shouldnt try to save
power by turning it off. But they do, says August. They
figure theyre going to save $10 on their summer utility
bill. Then we have a quick little power failure and the engine
wont start. They contact us and it ends up costing them
$500 for a service call. We remind all of our customers that
the generator is a piece of emergency equipment that has to
start up as quickly and easily as possible. All it takes is
a block heater that hasnt been installed properly, or
a burned-out block heater and a weak set of batteries to equal
a no-start situation. Depending on the application there could
be lives at risk.
At Kim Hotstart we used to issue maintenance manuals,
says Bass. We advised customers to check their heaters
at least once a year, perhaps remove the element and clean
out the tank. But weve discovered this doesnt
always happen. Once those heaters go on, a lot of people dont
do much to them unless they fail. Why do they fail? Various
reasons. Impurities in the cooling systems, bad coolant, and---a
big problem---mixing antifreeze incorrectly. And hard water
is one of the most common causes of heating element failure.
The surface temperature of the heating element causes the
minerals in the water to attach to the sheath. The minerals
collect to form an insulation layer that increases the internal
element temperature. As the insulation layer thickness continues
to increase, the element temperature eventually increases
to the point of failure---that is, the element burns itself
out. If this happens, the cooling system should be completely
drained and flushed. But putting a new heater in this environment
will not solve the problem. Whats required is using
de-ionized water, low-silicate antifreeze, and low-silicate
supplemental additives. And dont over-concentrate. Anything
over a 60-40 mix is very hard on our heating elements. Over-concentration
of coolant or additives will cause a gel-like slime to accumulate
on the element. In severe cases this may burn on the element
causing a black sludge to form, which decreases the heaters
efficiency.
Antifreeze should never be added to an engine without
being mixed with water first. If the antifreeze is added before
the water, it will sit at the bottom of the engine. Because
block heaters are designed to sit at the lowest point of the
water jacket and because water pumps will not mix the coolant
in the engine, if antifreeze is added without water, the heater
will be filled with pure antifreeeze and this will cause a
scale to form. Bass also notes that because engine coolant
reaches its hottest temperature inside the block heater, the
heater itself is a good diagnostic tool for cooling system
conditions that could have detrimental effects on the water
pump, the after cooler, the oil cooler and the radiator.
Its also important that the coolant level is
always up. Because, if you get an air pocket, the heated coolant
cant circulate and the heater will overheat and fail.
What you have to do then is thoroughly purge the engine to
eliminate any air pockets before the heater is energized.
We recommend running the engine up to operating temperature
to open the engine thermostat after installation, which insures
that no air pockets are left within the cooling system. Also
check the outlet hose and make sure there is no point in the
line where it flows down. Remember that heat rises, and a
downward trend will stop the flow of hot water.
The same is true with running the engine while the
heater is still energized. All of our stationary applications
either use an oil pressure switch---so when the engine starts
and begins to build oil pressure, it automatically turns off
the heater---or the system may be on something like a 24-V
or 12-V relay and, when the engine starts, the relay drops
the heater off the line. This is because if the heaters
on and the engine starts, the coolant is sucked out, and again
the heater is burning in open air and will fail. All
other things being equal, Bass says, drain the cooling system,
clean it, and flush it every two years---procedures he recommends
be specified in maintenance contracts.
What weve seen, says August, is sometimes
OEMs use a cheaper coolant and regular tap water, and the
block heater element will cake up very quickly. We use a premixed,
premium antifreeze and its mixed 50-50 with distilled
water. Block heaters should be part of a clients weekly
generator checks. It can be as simple as putting your hand
on the side of the engine block. Is it stone cold or nice
and warm? Fire up the engine for a couple of minutes. If the
block heater isnt working, its going to be difficult
to start. This puts an extra strain on the batteries, and
of course the engine is going to smoke.
Dauffenbach recommends other block heater items he considers
important to check during regular engine service, hoses for
example. Automotive type hoses last about five years.
Stainless steel braided hoses lined with silicone last for
20 years. For just a few dollars more youll have no
maintenance on your jacket water heaters for the life of the
engine/generator set. From his experience at the dealership,
Phillips agreesuse a silicone-based hose because the
silicone withstands high temperatures better. Once a
year, grab hold of your hoses and make sure theyre pliable.
Total Systems recommends hoses be changed at a minimum of
every three years. Block heater hoses have heat on them
all the time, 24/7, says August, as opposed to
a radiator hose, for example. They deteriorate much faster,
and if theyre not caught early enough, theyll
fail. Theyll burst open, the engine will lose all of
its coolant and the heater will burn out. We recommend silicone
hoses for more critical applications like hospitals.
Phillips reports that Caterpillar has begun installing circulation
pumps typically used with large engines on all its factory-installed
block heaters, including smaller models. Convection-type
heating is not a perfect world, says Phillips. The
jacket system has all these passages, which sometimes cause
the convection to get stuck. Then you get hot spots. I foresee
that in the future pumps are going to be standard, and I think
its a good idea. With pumps you can count on the entire
engine being warmed, and with pumps even more heat will be
distributed throughout the engine.
August isnt so sure and says if everythings plumbed
correctly there should be no need to install pumps on smaller
engines. He also recommends that, although block heaters are
common on diesel gen sets, natural gas engines should also
be equipped with block heaters. A block heater on a
gas engine will function the same and have the same advantages
as on a diesel engine. The engine will start quicker, the
heater will bring the oil up to temperature quicker, and this
will reduce wear. My basic recommendation is that anything
that can have a block heater on it should have one.
Journalist PENELOPE GRENOBLE O'MALLEY is a frequent
contributor to environmental publications.
DE - July/August 2005
|